Runtime
Under all normal running conditions, a 3–minute minimum ON and OFF timer is maintained for each
compressor. Once a compressor is turned ON, it remains on for a minimum of 3 minutes. Once a
compressor is turned OFF, it remains off for a minimum of 3 minutes. System overrides that require
an immediate shutdown of the equipment, test modes, and compressor diagnostics/protection functions
can override these 3–minute timers. However, for normal temperature and thermostatic-based control,
this minimum ON/OFF timers are maintained.
Click the e-library symbol for the latest version
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.