Issue:
Very Low Evaporator Refrigerant Pressure diagnostic may be annunciated after performing a circuit lockout. Unlike previous products, even if the circuit associated with the suction pressure is locked out, it will not defeat the protection afforded by this diagnostic.
Resolution:
To continue with the Circuit Lockout without the diagnostic, unplug the suction transducer on this circuit. It will generate a diagnostic Comm Loss: Suction Refrigerant Pressure but will allow the other circuit to run.
Notes:
Resource Available:
- Tech TV Video(s):
- N/A
- Reference Literature: (Electronic copies can be pulled from e-library at Trane Residential (tranetechnologies.com))
- IOM:
- Service Guide:
- Other:
- N/A
Changes:
Other Question/Problem/Cause Statements:
Facts:
- Air-Cooled Chiller