Problem:
There are times when the supply fan is OFF and the Event Log may show Outdoor Air Flow and Duct Static Alarms. These diagnostics are shown because the transducers that monitor these pressure readings will sometimes go below the units configured minimum operating range of 0 CCFM or 0 iwc. If your diagnostic(s) are persistent when the unit is placed in normal operation, please proceed to the following troubleshooting steps. IntelliPak (Symbio 800) - How to troubleshoot a Traq Flow Sensor Failures
Example:
Solution:
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.