Cooling only- Single stage DX
The CSTI (red) board is just a terminal interface:
- Remove jumper on 1TB1

2. Run those two wires to the condenser contactor.
3. Wire Y1 from the TSTAT to the TB3 terminal block 6.

NOTE: See complete schematic attached. Sample is Blower coil with DX