This covers the installation of low-leak economizers for 3 to 5-ton downflow and horizontal units.
Used With
| Model Number: | Used With: |
| BAYECON353* | E/GB*036-060 - E/GD*036-060 |
Installation Instructions
Click the e-library symbol for the latest version of the installation guide.
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.