Warning: Changing parameters on the TR150 VFD should only be done by individuals with adequate electrical and mechanical experience, and who comply with all relevant laws, rules, orders, or regulations. Improper installation, service, or repair may result in personal injury or property damage. The manufacturer or seller cannot be held responsible for any issues that arise from the interpretation or use of the information provided.
Problem: How do I change the parameters on a TR150 VFD?
Solution: Follow the steps below to adjust the VFD parameters. Follow example below to change parameter 1-20.
1. Stop the equipment either at the Human Interface or by pressing the Off/Reset button on the TR150 VFD.
2. Press the MENU key until the triangle is above "Main Menu".
3. Press the "Down" arrow until you reach parameter group 1.
4. Press OK.
5. Press the "Down" arrow until you reach parameter group 1-2.
6. Press OK.
7. Press the "Down" arrow until you reach the specific parameter 1-20.
8. Press OK.
9. Use the "Up" or "Down" arrow to change the value of the parameter. Alternatively, you can use the right arrow button to highlight a specific digit to change.
10. Press the OK button once you have made the desired changes.
11. Press the Back button to exit this parameter and navigate to the next parameter you want to adjust.