The Filter Runtime Hours running total can be checked by going to Status, Indoor.
If you see the following diagnostic, it is most likely caused by the Filter Runtime Hours counter reaching the Filter Runtime Hours Setpoint. (check at Settings, Indoor)
To reset the alarm
Go to Tools → Service → Filter Timer Reset → and press Reset
- Pro - It will get rid of the alarm when you press Reset
- Con - The alarm will come back when the timer expires again.
Optional
Go to Settings → Indoor and set the Filter Runtime Hours Setpoint to "0"
- Pro - You will never see this alarm again.
- Con - The Symbio Board will not remind you to change the filters.
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.