It has been brought to our attention that replacement R410A variable speed compressors (VSC) no longer list R410A as the refrigerant type and ONLY list R454B. This was a minor oversight by Danfoss and have verified that VZH (088/117/170) models with a Design Sequence (Design Pressure Ratio) of "C" have been qualified for use with both R410A and R454B refrigerants.
Danfoss is planning to change the label to show both refrigerants on the nameplate in future releases to ease any confusion.
VZH Nameplate Reference
Design Pressure Ratio (model digit 7 - "C") are rated for R410A and R454B. VZH compressors with model digit 7 (model digit 7 - "B") CANNOT be used with R454B applications.
Nomenclature
The example below presents the compressor nomenclature which equals the technical reference as shown on the compressor nameplate. Code numbers for ordering are listed in section Ordering.
| V | Z | H | 117 | C | G | A | M | A |
- V
- Variable speed
- Z
- Family
VZH scroll
- Family
- H
- Lubricant
POE Lubricant, R410A / R452B / R454B refrigerant
- Lubricant
- 117
- Swept volume
in cm³/rev
- Swept volume
- C
- Design pressure ratio C: with IDV
- G
- Motor voltage code to CDS803* or CDS303*
G: 380-490V/3~/50&60Hz
H: 525-600V/3~50&60Hz
J: 200-240V/3~50&60Hz
* main supply voltage to frequency converter.
- Motor voltage code to CDS803* or CDS303*
- A
Equipment version
A: brazed connection, oil sight glass
D: brazed connections, Oil level sensor+oil sight glassOil sight glass Oil level switch Oil sight glass Threaded None Oil level sensor+ oil sight glass Threaded Threaded
- M
- Motor protection type
M: no internal motor protection (protection by drive), multi-refrigerant
- Motor protection type
- A
- Evolution index
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.