Symbio Compressor Minimum Runtime
Summary:
For cooling-only units, a 3-minute minimum ON and OFF timer is maintained for each compressor. For Heat Pump units, a 5-minute minimum ON timer and a 3-minute minimum OFF timer are maintained for each compressor. Once a compressor is turned ON, it remains on for at least 3 or 5 minutes. Once a compressor is turned OFF, it remains off for at least 3 minutes. System overrides that require immediate equipment shutdown, test modes, and compressor diagnostics/protection functions can override these minimum run timers. For normal temperature and thermostat-based control, these minimum ON/OFF timers are maintained.
Click the e-library symbol for the latest version
You can download the ACC-APG002C-EN below
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.