Issue:
Transformer Sizing for Unit Controllers
Resolution:
Transformer Sizing for Unit Controllers
If you are providing a new transformer for power, use a UL listed Class 2 power transformer. The transformer must be sized to provide adequate power to the controller and output devices, including relays and valve actuators.
- Know your systems total power draw in volt-amps (VA)
- Convert all your devices ratings to this standard (VA) and add them up to get your total power requirement.
-Â Consider - inrush current (maximum, instantaneous input current drawn by an electrical device when first turned on)
- Is a good practice to calculate 30% to 50% more than the total VA for future expansion.
Â
Note: Loading a Transformer fully, even though it is supposed to be designed for it, will shorten its useable life due to excessive heat buildup inside the unit.
Â
Notes:
What is a Class II Transformer?
Transformer used to supply Class II circuits. Rating of less than 100 VA and a maximum secondary output of 30 VAC. The maximum VA generally offered is 75 and the most common secondary voltage is 24 VAC. Class II Transformers are either inherently or non-inherently limited.
Note: Class 2 circuits are limited to voltage and current values that will not usually present a shock or fire hazard.
Â
Inherently Energy Limited Class II Transformers - Class II transformers up to 50 VA are "Inherently Limited" which means that the transformer, if overloaded, will short itself out and fail safely, not requiring a fuse.
Â
Non-Inherently Energy Limited Class II Transformers - 60 thru 100 VA Class II transformers are generally protected by a resettable circuit breaker or a fuse within the transformer secondary. Without overload protection, the transformer would not satisfy the safety requirements for a Class II circuit.
Â
What is VA rating?
A volt-amp (VA) is basically just another unit for measuring power. Describes a quantity of electrical power used, supplied, or otherwise handled by an electrical or electronic device VA is the unit of choice for controls manufacturers.VA vs Watts
On a DC circuit, 1 VA is the equivalent of one watt (1 W). On an AC circuit, to convert from W to VA, multiply by 1.4, or to go the other way, multiply by 0.714. Note: Because most AC circuits contain reactance, the VA figure is greater than the actual dissipated or delivered power in watts.
Â
Other Question/Problem/Cause Statements:
- Transformer Sizing for Unit Controllers.
Facts:
- Sensors and Accessories
- Terminal Unit Controller (TUC)
- Thermostat Control Module (TCM)
- Tracer MP501
- Tracer MP503
- Tracer MP580/581
- Tracer UC400
- Tracer VV550/551
- Tracer ZN510/511
- Tracer ZN517
- Tracer ZN520/521
- Tracer ZN523
- Tracer ZN524
- Universal Programmable Control Module (UPCM)
- VariTrac Comfort Manager
- VariTrac II Central Control Panel (CCP)
- VariTrac III Central Control Panel (CCP)
Original wave: wave48451
Document Identifier: DOC-101621
Document Identifier: 101621