Issue:
CAN HE CHANGE THE ACTION OF THE REVERSING VALVE FOR A CCP RELAY BOARD CONTROLLING A HEAT PUMP?
Resolution:
No. It is always energized for cooling and can not be changed. A pilot relay could be used to control a reversing valve in the oposite direction. The normal default is TB1-7 open (unpowered) for heat and closed (powered) for cool.
Â
Other Question/Problem/Cause Statements:
- CAN HE CHANGE THE ACTION OF THE REVERSING VALVE FOR A CCP RELAY BOARD CONTROLLING A HEAT PUMP?
Facts:
- VARITRAC III CENTRAL CONTROL PANEL (CCP)
- VariTrac III Central Control Panel (CCP)
Original wave: wave1414
Document Identifier: DOC-76252
Document Identifier: 76252