Issue:
how should the VAV dips be set
Resolution:
CCP3 delivered VAV can talk to 32 VAV boxes
the VAV boxes must use the first 32 addresses
VAV-SVN03A-EN calls these 1 to 32
https://tranesupport.zendesk.com/hc/en-us/articles/11744522945677-VariTrac-III-CCP-literature
VAV-SVX01D-EN calls these, UCM unit # 1 to 32, Eware address 65 to 96
https://tranesupport.zendesk.com/hc/en-us/articles/14218601121165-VAV-UCM-literature
Summit would list the addresses for these boxes in the 65 to 96 range