Issue:
VAV with electric baseboard heat is not bringing on reheat. WHY?
Resolution:
Setup the reheats as staged hot water/perimeter
Other Question/Problem/Cause Statements:
- VAV with electric baseboard heat is not bringing on reheat. WHY?
Facts:
- VARITRAC II CENTRAL CONTROL PANEL (CCP)
- VAV is in the heat mode.
- VAV is configured with electric reheat.
- Reheat was actually electric baseboard.
- VariTrac II Central Control Panel (CCP)
- VariTrac III Central Control Panel (CCP)
- VAV UCM
- VAV nonLonTalk