Issue:
Trying to override the VAV boxes to max flow, but they stay at minimum position.
Resolution:
There must be a sensor connected to the VAV box or a Temperature Sensor Failure diagnostic will occur. When failed open, the UCM will control the valve as if very cold temperature exists in the space.
Â
Other Question/Problem/Cause Statements:
- Trying to override the VAV boxes to max flow, but they stay at minimum position.
Facts:
- Everyware Service Software
- Tracer Summit (OS/2)
- Tracer Summit (Windows)
- Tracer Summit Building Control Unit (BCU)
- VariTrac Comfort Manager
- VariTrac II Central Control Panel (CCP)
- VariTrac III Central Control Panel (CCP)
- VAV Command Unit I
- VAV Command Unit II
- VAV nonLonTalk