Issue:
what causes bypass calibration fail diagnostic
Resolution:
VAV-SVU01A-EN, operator guide, page 58, bypass calibration fail, calibration not successful
2 Bypass Calibration Fail = Indicates the CCP failed to complete the calibration process. Likely causes are failure to read zero flow (fan did not shut off or bad static pressure transducer), or failure to read a valid static pressure value with the fan on (system not balanced properly, oversized ductwork, or bad or improperly installed static pressure transducer).
VAV-SVU01A-EN, operator guide, page 11, bypass system calibration sequence, check that it happens
check the Kavlico pressure transducer on the change over bypass damper