Issue:
Can't increase the static pressure setpoint enough on a CCP. HOW?
Resolution:
There is a workaround for low static setpoint:
Remove the hoses from the bypass static pressure transducer.
Force the CCP III into calibration.
The CCP will fail calibration and use a default Static pressure setpoint of one half inch(0.5").
Hook the hoses back up to the transducer.
Use the static pressure multiplier to set the setpoint to the required value.
This will work until the next calibration.