Issue:
Will the ReliaTel DH sequence work when it is part of a VariTrac CCP3 change over bypass system?
Resolution:
The ReliaTel dehumidification sequence is NOT disabled.
The ReliaTel can run the DH sequence during no call for heating or cooling or Cool 1.
The DH is not allowed during heat or Cool 2.
Â
Other Question/Problem/Cause Statements:
- Will the ReliaTel DH sequence work when it is part of a VariTrac CCP3 change over bypass system?
- Does a VariTrac CCP3 change over bypass system disable the ReliaTel dehumidification sequence?
Facts:
- VARITRAC III CENTRAL CONTROL PANEL (CCP)
- VariTrac III Central Control Panel (CCP)
- Voyager/Precedent nonLonTalk
Original wave: wave82645
Document Identifier: DOC-103960
Document Identifier: 103960