Issue:
Can a CCP II communicate with a communicating Sensor-Bypass Assembly so a Summit BMTX can see the information
Resolution:
No the CCP to cannot use the communication bypass assembly because the Static pressure sensor and supply air temperature sensor needs to be hardwired to the CCP II. The bypass damper is also hardwired. So the Communicating Sensor-Bypass Assembly would communicate but the CCP could not recognize the data. The Summit then could not see the data.   Â
Notes:
The CCP III does not communicate to the Summit system so they use the CCPII as an interface between the Summit and a Varitrac system.
Changes:
Â
Other Question/Problem/Cause Statements:
- Can a CCP II communicate with a communicating Sensor-Bypass Assembly so a Summit BMTX can see the information
Facts:
- VariTrac Controls
Original wave: wave13114