Issue:
Does EMTK Tracker report the Voyager supply air temperature and the damper position?
Resolution:
Â
If you have an ECA or a RTEM module installed on the outside air damper with a mixed air sensor it will report this value for supply air temperature. It does not report the value from the supply air sensor wired to the RTOM.
If the ECA or RTEM does not detect a mixed air sensor on power up it will fail and damper position will also fail. If it had detected a mixed air sensor at power up and then it failed the supply air sensor would report -40 degrees and it would still report the damper position.
If the RTRM does not detect an ECA or a RTEM on Power up but has a RTOM with a supply air sensor it will report this value and of course will not report the damper position.
Â
Notes:
Changes:
Â
Other Question/Problem/Cause Statements:
- Does EMTK Tracker report the Voyager supply air temperature and the damper position?
- what sensor does the Tracker report for supply air temperature?
Facts:
- TRACKER EMTK
- Tracker EMTK
- Voyager/Precedent non LonTalk
Original wave: wave104479