Problem
WSHP variable speed fan will not Start 460 vac.
Resolution
With 460 vac incoming power, a dedicated Neutral wire is required to supply 277 vac power to the fan motor. This does not mean one leg of 460 and ground, but a dedicated neutral 4 power wire hook up. If not wired in this manor, or 460 vac applied to the ECM module, the ECM module will be blown and will need to be replaced.
Notes
ECM module part numbers, pricing, and availably can be found by contacting Trane Supply > Store Locator.
WARNING
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.