NOTE: Voltage measurements required to ID problem
On the schematic this is labeled P1-P8
1 and 5 = Line voltage
3 = DC common
4 = DC PWM signal
8 = RPM feedback from motor
7 = Earth Ground
2 and 6 = (115v units) Jumper present on the harness
Step 1: Initial Reset & Power Cycle
- Remove Run Command:
- ZN or UC Controllers: Set the zone sensor to OFF.
- CSTI Boards: Set thermostat or third-party building controller to OFF.
- Manual Fan Switch: If equipped with a unit or wall-mounted speed switch, switch to OFF.
- Cycle Main Power:
- Turn unit disconnect switch OFF for at least 15 seconds.
- Restore power to the unit.
Step 2: Disable Locked Rotor Protection (LrPt)
Disabling LrPt temporarily allows the board to send a continuous run command without shutting down after 5 seconds, enabling accurate electrical and mechanical diagnostics.
Programming Sequence (Blue ECM Control Board):
- Enter Menu: Press and hold the SET button for 3 seconds until the display reads
Hi1. - Navigate to LrPt: Press the MINUS (-) button 4 times until the display reads
LrPt. - Edit Parameter: Press the SET button once. The display will show
on. - Disable Setting: Press the MINUS (-) button once. The display will change to
off. - Save & Exit: Press and hold the SET button for 3 seconds to lock in the setting.
Note: Leaving LrPt set to off during troubleshooting prevents nuisance cutouts. Once troubleshooting and repair are complete, it can be re-enabled if desired.
Step 3: Run Command & Mechanical Verification
- Re-apply a fan run command from the wall thermostat, zone sensor, fan speed switch or commission mode with Symbio Controller.
- Observe motor response:
- If the motor runs normally: The issue is resolved if RPM is displaying on the ECM board (suggest leaving LRPT off or fix loose wire connection). Motor could be going bad internally however has not failed entirely.
- If the motor does NOT run: Continue to Step 4.
- Inspect wiring harnesses:
- Ensure all molex plugs, terminal block screws, and ground connections between the control board and motor are fully seated and tight.
Step 4: ECM Board Ramp Verification & Jumper Test
Observe the digital LED display on the blue ECM control board when a call for fan is active.
Scenario A: Display shows "Ramp" values (e.g., 100, 200, 300...)
- The ECM board is properly receiving a demand signal and calculating speed output. After the target RPM is reached ("Ramp" Stops displaying).
- Action: Proceed directly to Step 5 (Voltage Diagnostic).
Scenario B: Display does NOT ramp up
The board is not recognizing or receiving the operational demand signal.
- Test TB3 Bypass:
- Locate terminal block TB3 on the red board.
- Place a temporary jumper wire across TB3 Terminal 1 and TB3 Terminal 3.
(Note: This test is not available on UC400-B controllers). Use Commissioning mode to turn on the fan
- Evaluate Results:
- Motor runs correctly with jumper: The ECM board is functioning, but the upstream input signal is absent. TSTAT not sending 24v or Analog signal is not getting through the ECM board
- Motor still does not run with jumper: Either the signal to the ECM board is not getting through from the CSTI board or controller or the ECM board is not responding to the signal. Replace the Blue ECM Motor Board and the Red CSTI or adapter board.
Step 5: Motor Harness Signal Voltage Diagnostic
When the board indicates a ramp command but the motor fails to turn, test for the DC speed control signal at the motor connector plug.
Motor Plug Pin Configuration (Fan Coil 8-Pin Plug):
┌───┬───┬───┬───┐ │ 8 │ 7 │ 6 │ 5 │ (Upper Row) ├───┼───┼───┼───┤ │ 4 │ 3 │ 2 │ 1 │ (Lower Row) └───┴───┴───┴───┘
- Set your digital multimeter to DC Volts.
- Back probe or measure directly across Pin 3 and Pin 4 on the motor harness while the board is actively commanding fan operation.
- Expected nominal 3.8 VDC (Roughly 70% of 5VDC so 3.5 or less would be an odd voltage with a call for the fan to run) NOTE: This is M1HI and M2HI setting.
- Nominal operating range for FC product is .7 VDC to 3.8 VDC. Voltage will vary slightly with different meters and incoming AC voltage from the 24v transformer.
- .6VDC to 7VDC = continuity to the blue board with no call for the fan.
- Motor should start with 1VDC or more between P3 and P4.
Diagnostic Decision:
- 3.5 to 3.8 VDC IS present at Pins 3 & 4:
- Control voltage and line power are being delivered to the motor, but the internal motor electronics or windings have failed.
- Solution: Replace the ECM Motor.
- 0 VDC or less than 3.5 is NOT present at Pins 3 & 4:
- The motor is not receiving speed signal from the ECM board or harness.
- Check harness continuity from the board to the plug. If the harness is intact, Replace the ECM Motor Board and Red board (if equipped).
Quick Reference Summary
| Test Step | Observation | Root Cause / Required Action |
|---|---|---|
Power Cycle + LrPt Off | Motor starts and operates normally | Transient trip cleared; verify secure wiring. |
| Ramp Display | No ramp numbers on LED display | Perform TB3 jumper (Pins 1 & 3). |
| TB3 Jumper (1 to 3) | Fan starts with jumper installed | Upstream interface TSTAT or Controller issue |
| TB3 Jumper (1 to 3) | Fan fails to start with jumper installed | Motor if 3.8VDC at 3 and 4 or Boards if less that 3.5 VDC at 3 and 4. |
| Pins 3 & 4 Voltage | 1−3.8 VDC present, motor dead | Internal motor failure (replace ECM motor). |
| Pins 3 & 4 Voltage | 0 VDC during active call | Faulty harness or Red and ECM board output failure. |