Problem:
PPS Configurator error - Hardware type is not support by termination when using a WCI CO2 sensor.
PPS Configurator V5.2.
Tried changing the hardware type to none, the WCI reference is not allowed.
Workaround:
Easy workaround is to set the hardware type as not used and termination as uc600 software.
Point will need to be referenced on site to WCI sensors.
Solution:
Workaround is the only solution until the defect is fixed.
Status:
Defect in PPS Configurator V5.2
Next PPS Configurator build will fix the issue but time frame is TBD.