The Preferred method for configuring the unit controller is using the Phone App.
- Here is an article on where to get the App: Symbio - Where to download the Service & Installation Mobile Phone App
- Here is an article on configuring with the App: Symbio™ 700 - How to edit the equipment configuration
If a device with the App is not available, you can still edit the configuration.
User Interface Keypad
Description of the buttons displayed in the image above
1) Home Button / 2) Up Arrow Button / 3) Enter Button / 4) Left Arrow Button
5) Right Arrow Button / 6) Bluetooth Button / 7) Down Arrow Button / 8) Cancel Button
User Interface Button Description
| Button | Description |
|---|---|
| Up/Down | Allow the user to scroll the menus and submenus. |
| Left/Right | Allow the user to scroll between values for editable items. |
| Enter/Check Mark |
|
| Home | Tap to exit all submenues and return to the Home screen. |
| Bluetooth | Tap to go to the Bluetooth menu and initiate the Bluetooth device pairing sequnce. |
| Cancel | Tap to return to the previous menu level. |
How to Enter Edit Unit Config.
Steps found in the image above.
- Press the Home Icon.
- Scroll down, Select Utilities.
- Scroll down, Select Unit Config.
- Scroll Right, Select View Unit Config.
- Scroll down, Select Edit Unit Config.
Example to Change Config. in the Edit Mode
Unit Configuration based on Model Number
The link below has all the configuration tables by model number for Precedent, Odyssey, and Foundation units with the Symbio 700 controller.
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.