Issue:
How to reset memory on MP580
How to clear the controller
Resolution:
Go to the Configuration in Rover. From the Device menu, choose Reset Memory. This will remove all unit configuration, network configuration (DSN), and TGP programs.
If the MP580 is on a BCU site, Unassign it from the BCU before clearing the memory.
If the MP580 will not reset, cllick on the UnlockDevice in the Device menu of Configuration first. If security was ever set up this unit will be locked.
The other posibilty is the MP580 is unconfigured with the service LED flashing. Put it into a configured state and you will be able to reset memory
Notes:
Changes:
Other Question/Problem/Cause Statements:
- How to reset memory on MP580
- There is a TGP routine stuck in the MP580. How can I delete it?
- How do I clear out the MP580?
- How can I delete the configuration and the TGP routines in the MP580?
- Why can't I reset memory in the MP580?