The original fan motor used in some 3-5T Precedent units originally used a 2-speed motor that used a high-speed relay (HSR) to switch between high and low speeds.
Low-Speed Operation
- Motor ORG and BLK wires connected, RED & VIOLET powered
High-Speed Operation
- Motor ORG & RED isolated, BLK & VIOLET powered
The replacement motor may be a 3-speed motor with more wires than the original and different wire color designations (details from 3T unit using MOT18824 shown below).

Below is a wiring diagram that illustrates how to adapt this new 3-speed motor to the unit's 2-speed HSR wiring:

WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.