The Symbio Web UI allows the qualified service technician to access the control and change the point configuration using the steps below.
| 1. | Using the USB A to B cable, connect your PC to the USB port on the Symbio controller. | |
| 2. | Open a web browser and enter 198.80.18.1 into the address field. Select Login and follow the prompts. | |
| 3. | Select Points from the panel to the left. | |
| 4. | Select Binary Points from the header towards the center of the window. | |
| 5. | Enter the word "configuration" to filter the point names or scroll down and find the point named "Supply Fan Configuration Command". | |
| 6. | Left click the blue Supply Fan Configuration Command text. |
|
| 7. | Left click Configuration from the header. | |
| 8. | The top section of the screen is titled Point Settings. Find the Default Value dropdown and change the selection to Cycling. Select Save in the lower right corner. |
WARNING
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.