The motor terminals and insulators can be repaired and/or replaced using the enclosed procedures
GP Motor Terminal Replacement
- HCOM-SB-85
Notes
- The motor terminals and insulators can be repaired and/or replaced using this bulletin.
Tools
- Thomas & Betts Crimper - TBM-5/5S
- Die# - 13455 (Black)
- T&B reference
Additional details
Resource Available
-
Reference Literature: (Electronic copies can be pulled from e-library at Trane Residential)
- Other: GM-346_HR, HCOM-SB-85, GP-Terminals
Other Question/Problem/Cause Statements
- CHHN Motor Terminal Repairs
Facts
- RTAA 70-125 Ton (Pueblo)
- RTUA
- RTWA
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.