Compressor loads and unloads in large amperage jumps instead of gradually.
- Problem may be in either solenoid valves, 1U16 and/or 1U21 dual triac LLIDs, or with male piston in the compressor.
- Use process of elimination to find the source.
- Swap 1U16 and 1U21 LLID to see if problem follows or stays.
- Swap load/unload solenoid valve coils between compressors to see if problem follows or stays.
- If none of the above work, then the male piston on the compressor may need to be changed out. See RTAC-SVD02B-EN for instructions as well additional troubleshooting procedures for this model of compressor.
Additional details
Facts
- Air-Cooled Chiller (RTAC)
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.