What is the oil pressure for this chiller?
RTAA 130-400 ton - True oil pressure is not annunciated by the chiller. The RTAA 130-400 ton chiller uses a differential pressure switch to monitor the oil flow to the compressor. The switch is a normally closed switch that opens on a 50 psid drop across the oil filter circuit. Included in this circuit is the oil filter, master oil solenoid and a service valve. Typical pressure drop should be 20-25 psid with a clean (or new) oil filter.
Additional details
Other Question/Problem/Cause Statements
- What is the oil pressure for this chiller?
Facts
- Air-Cooled Chiller (Pueblo) (RTAA 130-400 Ton)
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.