The information below is for Pueblo built RTAA units.
- RTAA 70 - 158 tubes at 76.69 inches.
- RTAA 80 - 178 tubes at 76.69 inches
- RTAA 90 - 207 tubes at 76.69 inches
- RTAA100 - 236 tubes at 76.69 inches
- RTAA110 - 196 tubes at 112.4 inches
- RTAA125 - 248 tubes at 112.4 inches
The diameter of the tube is 0.625 inches and the wall thickness is 0.0228 inches.
Additional details
Other Question/Problem/Cause Statements
- Evaporator information for RTAA
Facts
- RTAA