CGAM Compressor Knocking Noise
- When the compressors run there is a knocking or banging sound. Often, this sound is mistaken for a bad bearing or loose scroll. This is likely a loose or improperly torqued mounting bolt on the compressor to chassis mounting.
- The solution can be found within the attached PowerPoint document
- All compressor mounting bolts will need to be loosened and tightening/torqued according to the instructions within the document
Additional details
Resource Available
- Reference Literature: (Electronic copies can be pulled from e-library at Trane Residential)
- IOM: CG-SVX17N-EN
- Other: CGAM
Facts
- Air-Cooled Chiller CGAM
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.