Rotary screw compressors are shipped from the factory without oil. A tag is attached to the compressor stating, "Notice Contains No Oil".
A good service practice when installing a helical rotary screw GP compressor (35-60 tons) or Intermediate (70-100 tons) is to add a small amount of oil before starting.
For GP compressors (35-60 tons)
- Relieve the nitrogen holding charge
- Remove the suction blank -off flange
- Remove the suction screen strainer
- Pour to 1 pint (and no more) of OIL00031 into the suction cavity
- Replace suction screen
- Bolt the suction line to the compressor
- Use a hand-oil pump and access the oil fitting on the front of the compressor to fill the internal oil filter
- Prime oil lines
For Intermediate compressors (70-100 tons)
- Relieve the nitrogen holding charge
- Remove the suction blank-off flange
- Remove the suction screen strainer
- Pour 1 to 2 pints (and no more) of OIL00031 into the suction cavity
- Replace the suction screen strainer
- Bolt the suction line to the compressor
- Prime the external oil filter with hand oil pump using the fitting on service valve
Notes
- This same procedure can be used for all Pueblo Screw Compressors
Additional details
Other Question/Problem/Cause Statements
- How much oil is added to a replacement Helirotor rotary screw compressor?
- Is oil added to a replacement rotary screw compressor?
- What does the tag "Notice Contains No Oil" mean?
Facts
- Compressors, Rotary
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.