What is the ACR evaporator heater power draw requirement?
Control VA includes operational controls only. It does not include evaporator heaters.
- A separate 115/60/1, 15 amp customer provided power connection is required to power the evaporator heaters
- ACR150T-165T; 800 watts
- ACR 180T-300T; 1200 watts
- ACR 375T-550T; 1600 watts
Notes
- Evaporator shell heat trace is not used on ACR units, just the immersion heaters for each waterbox.
Additional details
Facts
- Air-Cooled Chiller (Pueblo) (ACR)
Original HUB Document : DOC-207901
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.