Can I get HGBP on a screw chiller?
Hot gas bypass (HGBP) is not an available option from the factory, and Trane does not endorse its use on their screw compressors.
The competition provides hot-gas bypass in order to decrease compressor cycling. Hot-gas bypass falsely loads compressors, increasing kW intake and wasting energy. Trane's method is a 5-minute start-to-start and a 2-minute stop-to-start that allows our machines to match low load conditions.
Additional details
Other Question/Problem/Cause Statements
- Can I get HGBP on a screw chiller?
- Can I get hot gas bypass on a screw compressor?
- HGBP
- Compressor cycling
Facts
- Air-Cooled Chiller (Pueblo) (RTAA 70-125 Ton)
- Air-Cooled Chiller (Pueblo) (RTAC)
- Compressor Chiller (Pueblo) (RTUA)
- Water-Cooled Chiller (Pueblo) (RTHB)
- Water-Cooled Chiller (Pueblo) (RTHD)
- Water-Cooled Chiller (Pueblo) (RTWA)
- Air-Cooled Chiller (Pueblo) (RTAA 130-400 Ton)
- Air-Cooled Chiller (Pueblo) (RTAE)
Document Identifier: DOC-82615
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.