Is pump control mandatory for the RTUD chiller?
All RTUD units (systems with a remote condenser) REQUIRE that the chilled water pumps be controlled by the Trane CH530 to avoid catastrophic damage to the evaporator due to freezing.
It is strongly recommended that chilled water pump control also be used on RTWD to provide proper unit operation.
Additional details
Other Question/Problem/Cause Statements
- Is pump control mandatory for the RTUD chiller?
- Does RTUD chiller require pump control?
Facts
- Compressor Chiller (Pueblo) (RTUD 70-200 Ton)
- Water-Cooled Chiller (Pueblo) (RTWD)
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.