Compressor Starting Loaded
- Check condenser coils for cleanliness.
- Leaking load solenoid Refer to RTAA-SVD01A-EN (attached below): Intermediate compressor trouble shooting guide.
- Slide valve piston leaking Refer to RTAA-SVD01A-EN and RTAA-SVB09C: Piston replacement guide.
- Condenser fans not coming on. (check motor contactor, blade rubs, wiring, motor, etc...)
- Possible lip seal failure. Refer to RTAA-SVD01A-EN
Additional details
Other Question/Problem/Cause Statements
- Compressor Starting Loaded
- Compressor is starting up loaded.
Facts
- RTAA 130-400 Ton (Pueblo)
- Air-Cooled Chiller (Pueblo) (RTAA 130-400 Ton)
- RTAA 130-400 TON (PUEBLO)
- CHHB Compressor
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.