If the Symbio has an Advanced controller module from the factory, the Space Controller defaults to a Single Setpoint Zone Sensor. You can follow these steps to change from a zone sensor to a conventional thermostat control on a Symbio 700 Unit Controller Module.
Configuration Steps
- Click the Settings tab from the Home page on the Symbio Service & Installation App.
- Click the View Configuration tab from the Settings page.
- The Space Controller is set for a Single Setpoint Zone Sensor. In the top right corner, click the Edit button.
- Click the Proceed button.
- Click the Space Controller tab.
- Notice that the Apply button is disabled. The Apply button will be enabled once you change from a Single Setpoint Zone Sensor to a Convention T-Stat. Click the Apply button.
- Now you can see the change, but click the Apply button to SAVE that configuration.
- Click the Home tab at the bottom, and the thermostat inputs appear on the Home page.
Video
Images
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.