What voltage does the flow switch require on a CGAF?
- There is no field-supplied voltage required.
- The 24 Vdc voltage is supplied by the 1U48 CGM (Cold Generator Module)
- The flow switch should be wired across 1TB4-8 and 1TB4-9.
Additional details
Facts
- INTELLIPAK CHILLER 20-60
- Air-Cooled Chiller - Intellipak (CGAF)
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.