Balanced starts and hours on RTAC chillers is always enabled. It cannot be disabled.
The chiller will start the compressor which has the least amount of starts first. Then, it will stage on the next compressor which has the lesser amount of starts and continue this routine until all compressors are on.
When shedding compressors, the microprocessor will stage off the compressor which has the most amount of hours first, then stage off the next compressor which has the most hours and so on.
The microprocessor will not count a start until the female step solenoid valve steps in.
Additional details
Facts
- Air-Cooled Chiller (Pueblo) (RTAC)
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.