Quick Reference & Specifications
Learn how to physically locate and terminate serial (RS-485) and Ethernet communication lines on the Trane Symbio™ 700 controller, including bottom-left terminal block J17 polarity, daisy-chain terminals, and top-left RJ-45 Ethernet port connections.
| Attribute | Details |
|---|---|
| Applicable Controller | Symbio™ 700 |
| Serial Protocols | BACnet® MS/TP, Modbus™ RTU |
| Serial Connection Point | J17 Terminal Connector |
| Ethernet Protocols | BACnet®/IP, Modbus™ TCP |
| Ethernet Connection Point | Integrated RJ-45 Ethernet Port |
| Source Manual | Trane Symbio™ 700 Field Installation & Integration Guide (BAS-SVP085-EN) |
| Recommended Reference | BACnet® MS/TP Wiring & Link Performance Troubleshooting Guide (BAS-SVX51-EN) |
| Recommended Wire | Communication Wire – Trane Commercial HVAC Help Center |
BACnet® MS/TP & Modbus™
Serial communication wiring lands on the removable J17 Connector on the Symbio 700 board.
Terminal Details & Daisy Chaining
-
Polarity Sensitive: Observe correct polarity when connecting communication leads. Connect positive (
+) to+and negative (-) to-. -
Internal Common Shunt: The two
(+)terminals and the two(-)terminals on the J17 block are wired internally in parallel. -
Daisy Chain Wiring: Use the first set of
+/-terminals for the incoming comm trunk and the second set of+/-terminals for the outgoing run to the next device. This eliminates the need to splice two wires under a single screw clamp.
CAUTION: Polarity & Shield Grounding
Do not cross polarities: Inverted
+and-leads on any device on an RS-485 trunk will disrupt communication across the entire segment.Shield Grounding: Connect the drain/shield wire continuously through the network segment and ground at one end only (typically at the system controller/building automation panel), never at both ends.
MSTP Device ID and Baud Rate Using the Phone App: Setting up Symbio 700 MSTP Device ID and Baud Rate Using the Phone App – Trane Commercial HVAC Help Center
BACnet®/IP & Modbus™
For direct IP integration or high-speed building automation networks, use the integrated RJ-45 Ethernet port at the top-left corner of the Symbio 700 board (next to the USB-B service port).
For network installations using IP-based communications:
Connector: Standard 8-pin RJ-45 jack located on the Symbio 700 controller.
Cable Standard: Category 5e (Cat 5e) or Category 6 (Cat 6) shielded or unshielded twisted-pair (STP/UTP), terminated to EIA/TIA 568B standard.
Network Topology: Connect directly to the building automation system (BAS) Ethernet switch or field service router.
BACnet/IP Using the Phone App: Setting Up Symbio 700 BACnet/IP Using the Phone App – Trane Commercial HVAC Help Center
Communication Diagnostic Checklist
Before commissioning the controller via Tracer® TU or the Symbio Service App, verify the following physical checks:
License: Advanced license needed. The Symbio UC module display will show Symbio 700 Ready Advanced.
Physical Seating: J17 terminal block is firmly seated in its connector receptacle.
Wire Gauge: Use 18-22 AWG shielded twisted-pair cable for serial connections (RS-485).
Polarity Match: All devices sharing the J17 trunk match
(+)to(+)and(-)to(-).End-of-Line (EOL) Termination: Proper 120-ohm termination resistance applied at the physical end of the MS/TP trunk (if Symbio 700 is the final node).
Ethernet Link LED: When using BACnet/IP, verify that the green Ethernet Link/Activity LED is solid or flashing.
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.