How to backup and how to re-configure a unit with UC800 controller
The attached Power Point presentation show the process on how to save the complete unit configuration file for your records as well as how to use this same file to re-configure the unit in case of suspected corrupted software or UC800 replacement.
Make sure you have the latest version of TU installed on your computer.
Notes
- This process is intended for Pueblo units only, the process may be the same for other units with UC800 controller but has not been tested.
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.