What is the correct IFM flow switch setpoint?
-
RTAC and RTAE Chillers Chillers
- There are 5 different IFM flow switches used for RTAC Chillers. Four flow switches are used for water applications and one flow switch (15 cm/sec) for all glycol concentrations.
- The table below can help determine which is the correct flow switch setting. It will be helpful to know the following
- Chiller Capacity
- Standard or High Efficiency (digit 12 of the chiller model number)
- Evaporator connection pipe sizeTableTable for RTAE IFM flow switch selection
Table for RTAE IFM flow switch selection, attached below as RTAE IFM flow switch selection.xlsx.
-
RTAF Chillers
-
Glycol:
- 15 cm/sec flow switch for all gylcol applications
-
Water (based on Trane Select Assist selection):
- 35 cm/sec flow switch
- 45 cm/sec flow switch
- 60 cm/sec flow switch
Correct flow switch on existing chiller can be verified using Webcats. If application changes from original submittal, a new selection should be ran using TSA. Under the General Header, the correct flow switch setpoint could be identified.
-
Glycol:
-
RTWD Chillers
-
Glycol:
- 15 cm/sec flow switch
-
Water:
- 35 cm/sec flow switch
- 35 cm/sec flow switch
-
Glycol:
-
CGAM Chillers
-
Water:
- 60 cm/sec.
-
Glycol (based on TSA selection):
- 15 cm/sec flow switch
- 25 cm/sec flow switch
- 35 cm/sec flow switch
- 45 cm/sec flow switch
- 60 cm/sec flow switch
-
Water:
-
ACSA and ACRA/B Chillers
- All selections are specific to parameters selected within TSA. Refer to submittal for proper IFM flow switch setpoint.
Notes
Refer to IFM Efector Flow Switch Programming for information about programming the IFM Flow Switch. Submittal will have flow switch setpoint identified for application chiller was selected for. If application changes, TSA program should be utilized by salesperson to identify flow switch setpoint for new application
Additional details
Facts
- Water-Cooled Chiller (Pueblo)
- Air-Cooled Chiller (Pueblo)
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.
Issue:
What is the correct IFM flow switch setpoint
Resolution:
RTAC and RTAE Chillers Chillers:
There are 5 different IFM flow switches used for RTAC Chillers. Four flow switches are used for water applications and one flow switch (15 cm/sec) for all glycol concentrations.
The table below can help determine which is the correct flow switch setting. It will be helpful to know the following
- Chiller Capacity
- Standard or High Efficiency (digit 12 of the chiller model number)
- Evaporator connection pipe size
Table for RTAE IFM flow switch selection
RTAF Chiller:
Glycol:
- 15 cm/sec flow switch for all gylcol applications
Water (based on Trane Select Assist selection):
- 35 cm/sec flow switch
- 45 cm/sec flow switch
- 60 cm/sec flow switch
Correct flow switch on existing chiller can be verified using Webcats. If application changes from original submittal, a new selection should be ran using TSA. Under the General Header, the correct flow switch setpoint could be identified.
RTWD Chillers:
Glycol:
- 15 cm/sec flow switch
Water:
- 35 cm/sec flow switch
CGAM Chillers:
Water:
- 60 cm/sec.
Glycol (based on TSA selection):
- 15 cm/sec flow switch
- 25 cm/sec flow switch
- 35 cm/sec flow switch
- 45 cm/sec flow switch
- 60 cm/sec flow switch
ACSA and ACRA/B Chillers:
- All selections are specific to parameters selected within TSA. Refer to submittal for proper IFM flow switch setpoint.
Notes:
Refer to IFM Efector Flow Switch Programming for information about programming the IFM Flow Switch. Submittal will have flow switch setpoint identified for application chiller was selected for. If application changes, TSA program should be utilized by salesperson to identify flow switch setpoint for new application
Facts:
- Water-Cooled Chiller (Pueblo)
- Air-Cooled Chiller (Pueblo)
Document Identifier: DOC-105425
WARNING:
Information in this article is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience and who comply with all federal, state, and local laws, rules, orders, or regulations related to the installation, service, or repair of a heating or central air conditioning product. Any attempt to install, service, or repair a heating or central air conditioning product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpretation of the information contained herein, nor can it assume any liability in connection with its use.